NC-ST Optional Equipment
Every cooling towers can be equipped with several optionals,
selected according to ILMED IMPIANTI experience.
> VIBRASWITCH
The vibration switch is available, to monitoring the anomalous vibrations of the fan units. The device, operating on a on/off control, when the vibration reaches such a level as to become dangerous for good operation, the vibraswitch automatically disconnects the electrical circuit of the unit.
The vibraswitch is provided with a reset button and a reset coil remote control switch.
> ELECTRIC HEATERS
Electric immersion heaters are available factory installed into the basin of the cooling tower. The heaters are sized to keep at + 4-5°C the basin water temperature with an ambient air temperature of - 15°C and with the fans switched off. They are supplied complete of thermostat in weatherproof enclosure for outdoor use.
| ITEM | COOLING TOWER MODEL | kW | ITEM | COOLING TOWER MODEL | kW | |
| EMRS01090101 | /M1/, /P1/ | 5 | EMRS01030601 | /H2/ | 5,5 | |
| EMRS01030601 | /Q1/, /R1/ | 5,5 | EMRS01090101 | /M2/, /N2/, /P2/ | 2X5 | |
| EMRS01030601 | /Q2/, /R2/ | 2X5,5 |
> CAGED LADDER
For the inspection and maintenance of the fan units a caged ladder can be supplied, to climb over the fan deck. The caged ladder will be manufactured in HDGS.
> FAN DECK HANDRAIL
In case of supply of caged ladder, the safety handrail all around the fan deck is strongly recommended. The handrail is manufactured in HDGS, according to the most common international regulations. In any case the access to the fan deck has to be restricted to authorized and skilled personnel.
> MAKE-UP VALVE
A mechanical valve an float assembly is available for a simple water level control and make-up. Float valve is plugged in the water make-up manifold.
It allows to automatically make-up the water consumed for evaporation and other reasons. It is made by a copper or plastic floating sphere and a cast iron floating tap.
> WATER LEVEL CONTROL
The electric water level control is also available, for an accurate control of the basin level. It is a liquid point level switch based on the technology of the vibrating fork, to be assembled inside the basin of the cooling tower.
> TEMPERATURE SENSOR
An electric temperature sensor is available, to be assembled in the basin of the cooling tower, or preferably on the outlet piping. The sensor is made by an electric probe of the PT100 type, complete of transmitter 0-20 mA.
| OPTION | ELECTRIC MOTOR | FAN | SILENCERS | PWL Gain [dBA] |
| LNB | Low speed rotation | Special blade configuration | n/a | 4 - 5 |
| LNS | Very low speed rotation | Very low noise configuration | n/a | 9 - 10 |
| LLN | Very low speed rotation | Very low noise configuration | On fan discharge / Basin spalsh attenuator | 12 - 15 |
| ULN | Very low speed rotation | Very low noise configuration | On air discharge / Basin splash attenuator / Noise absorbing panels | 15 - 20 |
The figures are only for information. and not typical of one model of cooling tower. The actual figures of sound power level are issued in case of job, and are function of the design specifications